      SPECIFICATION OF 1.1 KV BUSHING

      Standard Particular Limits
      Creepage Distance 55 mm +
      Dry Power frequency withstand voltage 10 KV
      Wet Power frequency withstand voltage 10 KV
      Dry Power frequency withstand voltage 10 KV
      Tested for leakage at Air Pressure 70 degree °C & 3 Kg/Cm2

      SPECIFICATION OF 3.3  KV BUSHING

      Standard Particular Limits
      Creepage Distance 95 mm +
      Dry Power frequency withstand voltage 15 KV
      Wet Power frequency withstand voltage 15 KV
      Dry impulse withstand voltage 50 KV
      Tested for leakage at Air Pressure 70 degree °C & 5 Kg/Cm2

      SPECIFICATION OF 6.6/7.2  KV BUSHING

      Standard Particular Limits
      Creepage Distance 180 mm +
      Dry Power frequency withstand voltage 21 KV
      Wet Power frequency withstand voltage 21 KV
      Dry Impulse withstand voltage 60 KV
      Tested for leakage at Air Pressure 70 degree °C & 5 Kg/Cm2

      SPECIFICATION OF 10/11/12  KV BUSHING

      Standard Particular Limits
      Creepage Distance 275 mm +
      Dry Power frequency withstand voltage 28 KV
      Wet Power frequency withstand voltage 28 KV
      Dry Impulse withstand voltage 75 KV
      Tested for leakage at Air Pressure 70 degree °C & 7 Kg/Cm2

      SPECIFICATION OF 15/18  KV BUSHING

      Standard Particular Limits
      Creepage Distance 380 mm +
      Dry Power frequency withstand voltage 38 KV
      Wet Power frequency withstand voltage 38 KV
      Dry Impulse withstand voltage 95 KV
      Tested for leakage at Air Pressure 70 degree °C & 7.5 Kg/Cm2

      Specification for 22/24 KV  Bushing

      Standard Particular Limits
      Creepage Distance 590 mm +
      Dry Power frequency withstand voltage 50 KV
      Wet Power frequency withstand voltage 50 KV
      Dry Impulse withstand voltage 125 KV
      Tested for leakage at Air Pressure 70 degree °C & 7.5 Kg/Cm2

      Specification for 33/36 Kv  Bushing

      Standard Particular Limits
      Creepage Distance 850 mm +
      Dry Power frequency withstand voltage 90 KV
      Wet Power frequency withstand voltage 90 KV
      Dry Impulse withstand voltage 175 KV
      Tested for leakage at Air Pressure 70 degree °C & 8 Kg/Cm2